Operation with rated power (normal operation)
Rated data for mains voltage 400 V
4
Technical data
4.3
4.3.2
L
4.3-7
EDS82EV903-1.0-11/2002
Typical motor p ower
P
r
[kW] 15 22 30
Three-phase
C asynchronous motor
(4 pole)
P
r
[hp] 20 30 40
8200 vector type With mains filter E82EV153K4B3xx E82EV223K4B3xx E82EV303K4B3xx
Without mains filter E82EV153K4B2xx E82EV223K4B2xx
1)
E82EV303K4B2xx
1)
Mains voltage U
mains
[V] 3/PE AC 320 V - 0 % ... 550 V + 0 % ; 45 Hz - 0 % ... 65 Hz + 0 %
Alternative DC supply U
DC
[V] DC 450 V - 0 % ... 775 V + 0 %
Data for op eration with 3/PE AC 400 V or DC 565 V
Rated mains current
Without mains choke I
mains
[A] 43.5 - -
With mains choke I
mains
[A] 29.0 42.0 55.0
Output power U, V, W S
r
[kVA] 22.2 32.6 41.6
Output power +U
G
,-U
G
2)
P
DC
[kW] 10.2 4.0 0
Rated output current at 1kHzsin
chopper frequency
2kHzsin I
r
[A]
5)
32 47 59
4kHzsin
8kHzsin I
r
[A] 29 43 47
6)
16 kHz sin
4)
I
r
[A] 21 30 35
1kHz
2kHz I
r
[A]
5)
32 47 59
4kHz
8kHz I
r
[A] 32 47 59
16 kHz
4)
I
r
[A] 24 35 44
Max. permissible 1kHzsin
output current for 60 s
2kHzsin I
max
[A] 48 70.5 89
at chopper frequency
3)
4kHzsin
8kHzsin I
max
[A] 43 64 70
6)
16 kHz sin
4)
I
max
[A] 31 46 53
1kHz
2kHz I
max
[A] 48 70.5 89
4kHz
8kHz I
max
[A] 48 70.5 89
16 kHz
4)
I
max
[A] 36 53 66
Output voltage
without mains choke U
M
[V] 3~ 0 ... V
mains
/ 0 ... 650 H z
with mains choke U
M
[V] 3~ 0 ... approx. 94 % U
mains
/ 0 ... 650 H z
Power loss (operation with I
r8
) P
v
[W] 430 640 810
Required mains choke type] - ELN3-0075H045 ELN3-0055H055
Dimensions
with mains f ilter H x W x D [mm] 350 x 250 x 340
without mains filter H x W x D [ mm] 350 x 250 x 250
Weight
with mains f ilter m[kg] 34
without mains filter m[kg] 15
Printed in bold = Data for operation at 8 kHz chopper frequency (Lenze setting)
1)
Operation only with mains choke or mains f ilter
2)
For operation with power-adapted motors additional power to be t aken from the DC bus
3)
Currents for periodic load change: 1 min overcurrent with I
max
and 2 min basic load with 75 % I
r
4)
Chopper frequency is reduced to 4 kHz if Ï‘
max
reaches - 5 °C
5)
With different application conditions for other types possible: Operation with increased rated output current and
the same load change
(¶ 4.4-4)
6)
Operation only with automatic chopper frequency reduction (C144 = 1). Ensure not to exceed the declared
current s.