EasyManua.ls Logo

Lenze EMB934 Series - Page 107

Lenze EMB934 Series
206 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Fuses and cable cross−sections
5
107
EDBMB9340 DE/EN/FR 12.0
Shield connection system
ƒ Use an appropriate clip to connect the shield to the conductive mounting plate of
the control cabinet.
ƒ The connection should be as close to the cable end as possible.
ƒ If possible, cover the shield end with a shrink tube.
Remove
lacquer
Large−surface contact
of the cable shield
Shrink tube
Braid
Fig. 5−2 Shield connection
Carefully connect shields, ground connections (GND), and earth potential connections (PE)
to avoid interferences:
ƒ Do not interrupt shielding.
ƒ If an interruption cannot be avoided:
Connect the shields at interruptions (terminal strips, relays, fuses) with a large
surface and both ends to the mounting plate.
ƒ The cables must be laid as close as possible to the reference potential (dangling
cables are like antennas).
Earthing
Ensure a good equipotential bonding of all system parts (934x regenerative power supply
module, controller, mains filter etc.) by cables to a central earthing point (PE bar). The
minimum cross−sections of the cables must be strictly observed.
Filtering
ƒ Only use the filters assigned to the regenerative power supply module :
Mains filters reduce non−permissible high−frequency interferences to permissible
values.

Table of Contents

Related product manuals