Sicherheitshinweise
Sicherheitshinweise für die Installation nach UL/CSA
2
16
EDBMB9340 DE/EN/FR 12.0
2.3 Sicherheitshinweise für die Installation nach UL/CSA
Original − Englisch
Warnings!
ƒ Device is live up to 180 s after mains voltage disconnection.
ƒ Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V max, when protected by CC, J, T or R class fuses
(400/480 V devices).
ƒ Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any additional
codes.
ƒ Use 60/75 °C or 75 °C copper wire only.
ƒ Observe the specifications for fuses and screw−tightening torques in these
instructions.
ƒ Maximum surrounding air temperature 40 °C.