Electrical installation
Regenerative power supply modules EMB9341 and EMB9342
Control connections
5
115
EDBMB9340 DE/EN/FR 12.0
Wiring
Stop!
ƒ Do not lay control cables in parallel to disturbed motor cables.
ƒ Always shield the control cables as follows:
Use a screw to connect the shield sheet in the connecting area with the PE
surface.
Do not use the shield sheet for strain relief!
L3’ L2’ L1’ L3.2 L2.2 L1.2
Synchronization INPUT
OUTPUT
A1A2
3959
E1
L1 L2
L3
+UG -UG
0
1
9340vrm011
Fig. 5−7 Wiring of the control connections EMB9341 and EMB9342
Control connections
Shield sheet of control cable