Monitoring
Digital output monitoring
10
Network via CANopen
10.10
10.10.4
l
10.10-3
EDSPM-TXXX-3.0-04/2004
10.10.4 Monitoring of the analog outputs
Via the ind ex I6
443h
you can configure the reactions of the analog outputs, which
are to take place when no telegrams, ”node guarding events” or ”heartbeat” have
been received in the adjusted monitoring time.
z
Monitoring is started on receipt of the next PDO telegram after the settings.
z
If a telegram is not transmitted within the adjusted time, the module
switches to the ”Pre-Operational” state. No further process data are
transmitted.
z
A change into the ”Operational” state triggers a reset.
Index Name Possible settings Important
Lenze Selection
I6443
h
*
Error mode analog
output
0 {1} 255 Configures analog output monitoring
Index is only a vailable in the modular
system
E 10.10-3
0 All anal og outputs retain the last value output.
255 Response from I6444
h
In I6444
h
the response can be configured
individually for each analog output
1 Channel 1 0
2 Channel 2 0
... ... ...
36 Channel 36 0
Via index I6
444h
the response can be configured individually for each analog
output.
Index Name Possible settings Important
Lenze Selection
I6444
h
*
Error value analog
output
-32768 {1} 32767
Configures the individual analog output
responses
E 10.10-3
1 Channel 1 0
The analog outputs provide the set value
2 Channel 2 0
Index is only available in
he modular
... ... ...
sys
em
36 Channel 36 0
Individual response setting