8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00106
188 L Firmware 03.00 - DMS EN 5.0 - 07/2009
C00106
C00107
C00114
Parameter | Name:
C00106 | Auto-DCB: hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in C00019
.
Setting range (min. value | unit | max. value) Lenze setting
0.0 s 999.0 0.5 s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00107 | DCB: hold time
Data type: UNSIGNED_32
Index: 24468
d
= 5F94
h
Maximum hold time of the manual DC injection brake
In order to not overload the motor thermally, a time for automatic switch-off of the DC injection brake can be set
here.
Setting range (min. value | unit | max. value) Lenze setting
0.0 s 999.0 999.0 s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00114 | DIx inversion
Data type: UNSIGNED_16
Index: 24461
d
= 5F8D
h
Polarity of the digital inputs
Every digital input of the device can be inverted with regard to polarity via this bit field.
I/O terminals
Setting range (min. hex value | max. hex value) Lenze setting
0x0000 0xFFFF 0x8000 (decimal: 32768)
Value is bit-coded: (; =bit set) Info
Bit 0 DI1 inverted Inversion of digital input 1
Bit 1 DI2 inverted Inversion of digital input 2
Bit 2 DI3 inverted Inversion of digital input 3
Bit 3 DI4 inverted Inversion of digital input 4
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 ; RFR inverted Inversion of digital input CInh (controller inhibit)
; Read access ; Write access CINH PLC STOP No transfer COM MOT