PROFIsafe and PROFINET
Leuze electronic GmbH + Co. KG RSL 420P 102
11.4.11
Conclude configuration
Ä On the Devices tab, select
PLC > Compile > Hardware.
11.5 PROFINET project modules
During configuration, different module structures and their properties can be selected via Device Access
Points (DAPs) that are created in the GSDML file:
• DAP1: project modules [M1]…[M8] (see chapter 11.5.1 "Project modules for DAP1")
• DAP2: project modules [M11]…[M17] (see chapter 11.5.2 "Project modules for DAP2")
NOTICE
Ä DAP1 project modules are only available for PROFIsafe version 2.4.
Ä DAP2 project modules are available for PROFIsafe versions 2.4 and 2.6.
NOTICE
Ä The DAP 2 project modules can only be used in combination with a device firmware version
of 5.4 or higher and a connection unit firmware version of 2.0 or higher.
NOTICE
If the scanner is separated from the PROFINET communication unit, the connection is automati-
cally terminated and the communication channel is blocked. In this state, the configured mod-
ules no longer update any data. The switch functionality of the PROFINET connection continues
to exist.
11.5.1
Project modules for DAP1
Modules [M1]…[M8]
• For devices with M12 connection unit (CUM12):
• DeviceID: 0x0011