Mounting
Leuze electronic GmbH + Co. KG RSL 420P 52
NOTICE
With protective field boundaries <200mm, object detection may be restricted owing to the mea-
surement error.
Ä When defining the protective field, take into account the additional distance Z
sm
to the pro-
tective field contour (see chapter 7.2 "Stationary danger zone guarding").
• Configure the protective field so that the safety-related switching outputs are switched off from every
accessible point with sufficient minimum distanceD.
• Determine the start-up/restart operating mode required for the application.
• If you are using start and/or restart interlock, determine the position for the reset button.
• Many safety-relevant parameters are preset for each application in the configuration and diagnostics
software. Use these preset values where possible.
• Determine the conditions for the field pair changeover and the sequence of the field pair changeover.
Ä Create a record document for the device configuration and protective field dimensioning.
• The document must be signed by the person responsible for the configuration.
• Include this document with the machine documentation.
Ä Mark the protective field boundaries on the floor.
You can easily test the safety sensor along this marking.
After mounting, you can electrically connect (see chapter 8 "Electrical connection"), start up, align (see
chapter 10 "Starting up the device"), and test (see chapter 12 "Testing") the safety sensor.
7.1.4
Mounting examples
all dimensions in mm
1 Safety sensor
2 Column
3 BT856M mounting bracket
Fig.7.4: Example: mounting on a post