Technical data
Leuze electronic GmbH + Co. KG RSL 420P 153
all dimensions in mm
Fig.16.12: Mounting bracket BT856M, view A
16.4 PROFIsafe status profile
The PROFIsafe configuration modules contain all logical and electrical signals that are present in the safety
sensor. The signal names are used consistently throughout the configuration and diagnostics software (de-
vice DTM), in the event log and in the data telegram.
PROFIsafe project modules
During configuration, different module structures and their properties can be selected via Device Access
Points (DAPs) that are created in the GSDML file:
• DAP1: project modules 1…8
16.4.1
Project modules for DAP1
Modules [M1]…[M8]
• For devices with M12 connection unit (CUM12):
• DeviceID: 0x0011
• Textual designation for configuration:
RSL400PM12
• For devices with AIDA connection unit for copper cables (CUAIDA):
• DeviceID: 0x0012
• Textual designation for configuration:
RSL400PAIDA
• For devices with AIDA connection unit for fiber-optic cables (CUAIDA-OF):
• DeviceID: 0x0013
• Textual designation for configuration:
RSL400PAIDA-OF
• For devices with connection unit with L-coded M12 connectors/sockets for the voltage supply
(CU4M12):
• DeviceID: 0x0016
• Textual designation for configuration:
RSL400P4M12