24 – Control CS 320 / Rev.D 1.01 Control CS 320 / Rev.D 1.01 – 25
5.20 5.20 Connection of LCD monitorConnection of LCD monitor
Full access to all menu settings and parameters of the
controller is possible via the LCD monitor.
Ô “8.Programming”
Plug-in base X8
5.20 / 1
ATTENTION!
Property damage due to improper installation!
The LCD monitor must be plugged in whilst de-energised.
Only an LCD monitor from Marantec Legden
(art. no. 91447) may be used.
ATTENTION!
Property damage due to improper installation!
The Marantec Legden LED module (art. no. 103239) cannot
becombinedwiththeCS320.Useandcommissioningcan
leadtodestructionoftheCS320circuitboard.
5.20 / 2
Installation
5.21 5.21 Connection of MS BUS componentsConnection of MS BUS components
Two BUS interfaces are present on the circuit board for
connecting different components.
TheMS-BUSLCDmonitor(#121246)issuppliedwitha3m
long connection cable.
The MS-Bus LCD monitor (like the standard LCD monitor)
permits full access to all parameter settings.
It is possible to expand functions or realise additional
functions with the MS BUS function modules.
− ES module: Evaluation of trap-in protection
systems
− I/O module: Input/output expansion
− GV module: Two-way control
Connector strip X16 / X17
B
A
5.21 / 1
A ES module Connection to X16 or X17
B I/O module / GV module Connection to X16 or X17
C LCD monitor Connection to X16 only
REFERENCE
For a precise description of the function and connection,
refer to the separate documentation for the BUS modules.
NOTE:
The connector strips X16 and X17 can only be assigned once.
However,multipleBUSmodulescanbeconnectedthrough
special bypass cables.
The current consumption must be considered with this.