50 – Control CS 320 / Rev.D 1.01
10.5 Diagnosis operating mode / error memory
Display Meaning Condition
UPPERSWITCH UP limit position OFF: Limit position reached.
ON: Limit position not reached.
LOWERSWITCH DOWN limit position OFF: Limit position reached.
ON: Limit position not reached.
UP-SWITCH Command button / input OPEN ON: Button is actuated / input is active.
OFF: Button not actuated / input not active.
DOWN-SWITCH Command button / input CLOSE ON: Button is actuated / input is active.
OFF: Button not actuated / input not active.
INPUT 1 Programmable INPUT 1
(X4 / 9 + 10)
ON: Input 1 is active.
OFF: Input 1 is not active.
INPUT 2 /
SKS OPEN 2 /
SAFE. 2
(optionally)
Programmable INPUT 2
(X4 / 11 + 12)
Input dependent on MOD selected at
the programmable input.
INPUT 2 with MOD 5-7
SKS OPEN 2 with MOD 3-4
SAFE. 2 with MOD 2
ON: Input 2 is active.
OFF: Input 2 is not active.
—: Not activated.
INPUT 3 Programmable INPUT 3
(X10 / 1 – 3)
ON: Input 3 is active.
OFF: Input 3 is not active.
—: Not activated.
SKS Closing edge protective device 1
(DW,8.2kΩorphoto-sensor)
or light grid 1
(PNP or photo-sensor)
(X4 / 5-8) CLOSE direction
ON: System is closed.
OFF: System is interrupted (fault).
SKS 3 /
SAFE. 3
(optionally)
Closing edge protective device 3
(8.2kΩorphoto-sensor)
Radio transmission system channel 1
OPEN or CLOSE direction
Display dependent on MOD selected at
parameter SKS 3.
SKS 3 with MOD 2-3
SAFE. 3 with MOD 4
ON: System is closed.
OFF: System is interrupted (fault).
—: Not activated.
SKS 4 /
SAFE. 4
(optionally)
Closing edge protective device 4
(8.2kΩorphoto-sensor)
Radio transmission system channel 2
OPEN or CLOSE direction
Display dependent on MOD selected at
parameter SKS 4.
SKS 4 with MOD 2-3
SAFE. 4 with MOD 4
ON: System is closed.
OFF: System is interrupted (fault).
—: Not activated.
Functional overviews