Control CS 320 / Rev.D 1.01 – 39
Function Description
Adjustment
options
Factory setting
INPUT 1 Selection of a function that should be assigned to input 1 (X4 / 9+10).
MOD1: Button Sect. UP ......................................NO
MOD2: Switch Sect. UP ......................................NO
MOD3: Switch auto CL. ......................................NO
MOD4: External CLOCK (permanent UP) ............................NO
MOD5: Switch BMA 3 (Sect. opening) .............................NO
MOD6: Switch BMA 1 (emergency closing) ..........................NO
MOD7: Switch BMA 1 (emergency closing) ..........................NC
MOD8: Switch BMA 2 (emergency opening) .........................NO
MOD9: Switch BMA 2 (emergency opening) .........................NC
MOD10: Button ventilation function (Sect. opening) ....................NO
MOD11: Button automatic closing ..................................NO
MOD12: Laser scanner (height detection) ............................NO
MOD13: Switch BMA 3 (Sect. opening) .............................NC
MOD14: Slip door locking ......................................NO
MOD15: Light barrier 2 ......................................NC
MOD16: Forewarning switch ......................................NO
MOD17: Impuls button ......................................NO
MOD18: Crash sensor ......................................NC
MOD19: Lock operation commands via LCD monitor ...................NC
MOD22: Monitoring an external load contactor ........................NO
MOD30: UP switch inside ......................................NO
MOD31: UP switch outside ......................................NO
MOD32: DOWN switch ......................................NO
(only active with functioning closing edge protective device and
functioning light barrier 1. No function in dead-man’s operation.)
MOD1 – MOD19
MOD22
MOD30 – MOD32
MOD1
INPUT 2 Selection of a function that should be assigned to input 2 (X4 / 11+12).
OFF: NOT active
MOD2: Safety switching with resistance evaluation .................. xx Ω
MOD3: Switching strip – active in UP direction ...................8.2 kΩ
Stops and reverses with actuation
MOD4: Switching strip – active in UP direction ...................8.2 kΩ
Stop and rev with actuation
MOD5: Battery operation ......................................NO
MOD6: Radar movement detector (height detection) ...................NO
MOD7: Light grid 2 (SSR / PNP) with testing .........................NC
MOD9: Safety element - STOP with deviation .......................OSE
MOD10: Switching strip – active in UP direction ......................OSE
Stops and reverses with actuation
MOD11: Switching strip – active in UP direction ......................OSE
Stop and rev (2 sec.) with actuation
MOD12: Light grid 2 without testing ...............................OSE
Withrstcommissioningandafterareset,input2issettoA-self-teachingonce.If
a resistance value is detected, MOD2 (safety input 5.14) is automatically set and the
measured value is stored and monitored as a reference for the connected safety-
related components.
A single switching strip 8.2 kOhm (MOD 3/4) must be manually activated.
If no connected component is detected during initial commissioning or after a reset,
the input is automatically deactivated. OFF appears in the display and the input must
be manually activated.
A (teaching)
OFF
MOD2 – MOD12
A
INPUT 3 Selection of a function that should be assigned to input 3 (X10/1-3).
MOD4: Week timer
MOD21: Brake actuation monitoring
MOD22: (analogous to input 1/MOD22)
NOTE:
If MOD14 - 16 is set at relay 4, MOD 21 (brake monitoring) is automatically set at
input 3. This setting cannot be changed if the brake mode is active.
MOD4 / MOD21/
MOD22
MOD4