40 – Control CS 320 / Rev.D 1.01
Function Description
Adjustment
options
Factory setting
SKS3 Setting for channel 1 of the pluggable signal transmission system (X20).
OFF: Not active
MOD2: Activates as closing edge protection in DOWN direction.
MOD3: Activates as closing edge protection in UP direction.
MOD4: Activates as safety device (internal safety circuit)
If the pluggable component of the signal transmission system is plugged into X20, the
controller recognises this (only during initial commissioning or after a reset) and the
parameter is automatically set to MOD4.
A - (teaching)
OFF
MOD2 – MOD4
A
SKS4 Setting for channel 2 of the pluggable signal transmission system (X20).
Selection mode analogous to the settings under SKS 3.
A - (teaching)
OFF
MOD2 – MOD4
A
RUNNING-
TIME
Monitoring the maximum running time of an UP or DOWN movement.
During the teach-in run, the runtime of the door is learned automatically.
If the deviation is 20% (in both directions), a runtime error appears.
After automatic teach-in, the runtime can be changed manually.
A (teaching)
OFF
1 – 300 seconds
A
REVERS.TIME Motor standstill time with each direct change of direction.
The reversal time when the safety edge is activated during the closing movement is
one quarter of the set time.
100 –
5000 milliseconds
300
LIMIT SW. Selection of the limit position system to be evaluated.
MOD1: Absolute value encoder (AWG)
MOD2: Mechanical limit switches (MEC)
MOD4: only for frequency converter operation
MOD5: Absolute value encoder (AWG) + mechanical limit switch DOWN (NC)
with standard installation
MOD6: Absolute value encoder (AWG) + mechanical limit switch DOWN (NC)
withspecialinstallationwithleftrotatingeld
MOD 5+6 (optional):
Hereanadditionalexternalmechanicallimitswitchissettoquerythelowerendpoint
in order to compensate for tolerances caused by the door mechanism and/or the door
curtain. As soon as the mechanical limit switch is actuated, the lower end position is
considered reached, regardless of the information from the absolute encoder.
A (teaching)
MOD1 – MOD2
MOD4 – MOD6
A
SELF LOCK Selection between pulse operation and manual operation (dead man) with or without
evaluation of closing edge safety device (SKS) and light barrier system (LB).
MOD1: Pulse operation for OPEN + CLOSE with SKS and LB
With defective safety equipment, switch over to manual operation.
MOD2: Manual operation for OPEN + CLOSE with SKS and LB
MOD3: Manual operation for CLOSE, pulse operation for OPEN, with SKS and LB
MOD4: Manual operation for OPEN, pulse operation for CLOSE, with SKS and LB
MOD5: Manual operation for OPEN + CLOSE without SKS and LB
MOD6: Manual operation for CLOSE, pulse operation for OPEN, without SKS
andLB
MOD7: Manual operation for OPEN + CLOSE with SKS and LB
STOP upon reaching the intermediate position CLOSE.
By pressing the button again, continued travel to end position CLOSED
is possible.
MOD8: Pulse operation for OPEN + CLOSE with SKS and LB
With defective safety equipment, switch over to manual operation only
via circuit board button
MOD9: Manual operation for OPEN + CLOSE with SKS and LB
With defective safety equipment, operation only via circuit board button.
MOD1 – MOD9 MOD1