Control CS 320 / Rev.D 1.01 – 41
Function Description
Adjustment
options
Factory setting
POWER Automatic power monitoring
(Monitoring of the rotational speed)
Faultmessageintheeventofthedoorbeingdifculttomoveorblocked.
Adjustment of the sensitivity for OPEN direction.
A value for the force (rotational speed) will be displayed during opening.
With the power monitoring active, the value must be set to a lower value than the
lowest value shown during the door travel. The greater the difference to the lowest
displayed value, the less sensitive the reaction of the power monitoring.
The power monitoring is only activated if the numeric value is set.
OFF
1 – 999
10
RESET
MSBUS
All assigned MSBUS addresses are reset.
After a controller restart, re-addressing of all connected MSBUS devices takes place.
Ô For detailed information refer to the manual for the MSBUS device.
ON
OFF
OFF
RESTART With activation of the function, the controller is restarted. ON
OFF
OFF
FACTORY SET. Selection of the parameter set that should be reset with a RESET.
MOD5: Marantec Legden S Drives in dead man operation
MOD6: Marantec Legden FU Drive series MDF-U (integrated UPS)
MOD7: Marantec Legden S Drive series STAW with increased switch-on
duration
MOD8: Marantec Legden FU Drive series MTZ 05 (230V)
MOD9: Marantec Legden FU Drive series STA
MOD14: Marantec Legden FU Drive series MTZ 05 (400V)
MOD28: Marantec Legden S Standard with brake actuation.
MOD31: Marantec Legden S Dead-mans function, not resettable
MOD32: Marantec Legden DUO DUO-system, 2 drives
MOD99: Marantec Legden S Standard
MOD10–MOD13/MOD15–MOD97:Customer-specicparametersets
MOD5 – MOD99 MOD99
RESET Reset control parameters to the pre-selected factory settings.
MOD1: Part reset 1 (everything apart from frequency converter settings)
MOD2: Part reset 2 (everything apart from limit positions / known limit position
system)
MOD3: Complete reset (everything is reset to factory settings)
OFF,
MOD1 – MOD3
OFF
PIN no. 2 Input and selection of a PIN code for programming a service interval.
After inputting the PIN code, the second programming level opens.
Afterwards, a service interval can be entered via the SERVICE parameter. Input level 2
disappears again after the voltage is switched off, or automatically after 10 minutes.
AchangetothePINcodecanonlytakeplaceinthesecondprogramminglevel.
0 – 9999 1111
SERVICE OFF: Service display not active
Setting a service interval. After the set load cycles are complete, a service message is
issued (LED / LCD). If a relay output is programmed with MOD31, the respective relay
(continuous signal) switches.
Only appears after activation of input level 2 via parameter PIN no. 2.
OFF
0 – 99950
OFF
INVERTER Activates or deactivates a connected frequency converter. By connecting a frequency
convertertointerfaceX18thecontrollerbecomesanCS320FU.
Ô FordetailedinformationrefertothemanualfortheCS320FU.
MOD1: Operation without frequency converter
MOD2: Operation with frequency converter
MOD3: Operation with frequency converter (effective ramp times)
MOD1 – MOD3 MOD1