16 – Control CS 320 / Rev.D 1.01 Control CS 320 / Rev.D 1.01 – 17
EN
5.12 Terminal assignment, relay outputs
Four potential-free relay outputs are available, which can be
programmed with a variety of types of function.
Ô “10.2Inputoperatingmode”
1
2
3
4
5
6
7
8
X5
5.12 / 1
- Relay 1
- Relay 2
- Relay 3
- Relay 4
Internal
relay switch
contacts
There are four potential-free relay outputs able to take a max.
load of 4A at 230 V/1~.
The type of function depends on the parameter setting for the
respective relay output in the INPUT operating mode.
5.13 5.13 Connection of programmable inputsConnection of programmable inputs
ThecontrollerCS320has3programmableinputs,forwhich
different functions can be selected.
The type of wiring is determined on the basis of the
parameter settings for the individual inputs.
Ô “10.2Inputoperatingmode”(ParameterINPUT1-3)
ATTENTION!
Danger of damage to the circuit board due to
incorrect connection!
Inputs 1, 2 and 3 have different reference potentials and
must not be operated from a common potential!
Input 1
Optional wiring with NO / NC contacts.
Reference potential 24V-DC
Ô “10.2Inputoperatingmode”(ParameterINPUT1)
*
X4
5.13 / 1
* optionally

Table of Contents