18 – Control CS 320 / Rev.D 1.01 Control CS 320 / Rev.D 1.01 – 19
Installation
Input 2
Optional wiring with components on a 8.2 kOhm basis,
NO / NC contacts and photo sensors.
Reference potential 12V-DC
Ô “10.2Inputoperatingmode”(ParameterINPUT2)
* * *
1
2
3
4
5
6
7
8
9
12
GN
BN
WH
11
10
X4
8K2
5.13 / 2
* optionally
Legend:
GN Green
BN Brown
WH White
NOTE:
Programmable input 2 can also be used for the connection
of a light grid.
Ô “5.11Lightgridconnection”
Programmable input 2 is also used as a safety input in
accordance with EN 12453:2017.
Ifaresistancevalueisdetectedwithrstcommissioning
and after a reset, the MOD2 (safety input) is activated
automatically. Individually connected closing edge protective
device 8.2 kOhm must be activated manually in this case.
Ô “5.14SafetyinputperEN12453”
Input 3
Connector strip for optional wiring with pluggable week timer,
pluggable brake monitoring module BWM1 or as connection for
monitoring an external load contactor and drive brake.
Reference potential 5V-DC
Ô “10.2Inputoperatingmode”(ParameterINPUT3)
13:28
26.04.20
M
OK
20
B
X10
A
+ 5V
GND
IN
1
2
4
3
*
5.13 / 3
* optionally
A Week timer
The week timer offers a weekly program for opening the door
system and keeping it open with up to 8 switching times per day.
While the door is held open, the timer emits a continuous signal
that prevents the door system from closing.
After the set time interval has expired, this continuous signal
is switched off and the door system can be closed again, e.g.
manually via a CLOSE command.
Alternatively, automatic closing is also possible.
For this purpose the parameter OPEN TIME = 1 must be set in
the input operating mode.
B Brake monitoring module BWM1
The brake monitoring module is required for drives with a
brake connected (relay 4 / MOD 14-16). The module monitors
the brake function.
C Monitoring an external load contactor and
drive brake (optional)
Ô “5.13/5”