48 – Control CS 320 / Rev.D 1.01
MOD Description Remarks
MOD13 Switch BMA 3 (Sect. opening) NC Controlfunctionwithanactiverealarmsystem.
Closed: Normal function.
Open: Sect. opening of the door. The intermediate OPEN position (SECT. OPEN) is approached
from both directions, irrespective of the current door position.
BUTTON: no function.
LB / SKS: Door stops and moves clear (only in CLOSE direction), after
5secondsrenewedclosing.
STOP: Interruption of the emergency closing for the duration of activation.
MOD14 Slip door locking Monitoring limit switch for the pneumatic locking system of slip doors. The limit switch must have
conrmedthecorrectlockingwithin10secondsafteranOPENcommand,otherwiseanerrormessageis
issued and the door stops.
This function acts on relay mode 36.
MOD15 Light barrier 2 NC If a second light barrier is connected in the passage area of the door, this system can be programmed via
the parameter LB FUNC 2 in the INPUT.
Only connection of light barriers with potential-free NC contact.
MOD16 Forewarning switch Closed: Start-up warning and forewarning are inactive (even if both times > 0).
Open: Start-up warning and forewarning are active (only if both times > 0).
Ô “10.2Inputoperatingmode”
MOD17 Impuls button outside Pressing the button moves or stops the door.
– Function and direction of the movement depend on the IMPULS parameter setting in the input menu.
Ô “10.2Inputoperatingmode”/IMPULSparameter
– With active two-way control, this pulse command is treated as an external signal.
MOD18 Crash sensor NC Query of a crash sensor as NC contact. If the crash sensor was actuated once, only renewed door travel is
possible.
– after pressing and holding the STOP button for more than 5 seconds, or
– switching the supply voltage off and back on.
MOD19 Switch block operation commands
NC
Closed: no restrictions.
Open: It is no longer possible to use the (+) and (-) buttons on the LCD monitor and the
motherboard to issue operation commands in AUTOMATIC mode.
MOD22 Monitoring an external load
contactor
In a control version with external load contactor (motor power > 2.2kW / 8A) the auxiliary contacts of
the load contactor (NO) are connected and monitored here.
MOD30 UP switch inside Pressing the button opens the door to the UP limit position.
Theinternaltrafclightswitchestogreen.
MOD31 UP switch outside Pressing the button opens the door to the UP limit position.
Theexternaltrafclightswitchestogreen.
MOD32 DOWN switch Pressing the button closes the door to the DOWN limit position.
Only active with functioning closing edge protective device and functioning light barrier 1. No function in
dead-man’s operation.
Functional overviews