Control CS 320 / Rev.D 1.01 – 47
MOD Description Remarks
MOD5 Switch BMA 3 (Sect. opening) NO Controlfunctionwithanactiverealarmsystem.
Open: Normal function.
Closed: Sect. opening of the door. The intermediate OPEN position (Sect. OPEN) is approached
from both directions, irrespective of the current door position.
BUTTON: No function.
LB / SKS: Door stops and moves clear (only in CLOSE direction), after
5secondsrenewedclosing.
STOP: Interruption of the emergency closing for the duration of activation.
MOD6 Switch BMA 1 (emergency closing)
NO
Controlfunctionwithanactiverealarmsystem.
Open: Normal function.
Closed: Emergency closing of the door.
BUTTON: No function.
LB / SKS: Door stops and moves clear, after 5 seconds renewed emergency
closing.
STOP: Interruption of the emergency closing for the duration of activation.
MOD7 Switch BMA 1 (emergency closing)
NC
Controlfunctionwithanactiverealarmsystem.
Closed: Normal function.
Open: Emergency closing of the door.
BUTTON: No function.
LB / SKS: Door stops and moves clear, after 5 seconds renewed emergency
closing.
STOP: Interruption of the emergency closing for the duration of activation.
MOD8 Switch BMA 2 (emergency opening)
NO
Controlfunctionwithanactiverealarmsystem.
Open: Normal function.
Closed: Emergency opening of the door.
BUTTON: No function.
LB / SKS: No function.
STOP: Interruption of the emergency opening for the duration of activation.
No automatic closing after deactivation of the BMA signal.
MOD9 Switch BMA 2 (emergency opening)
NC
Controlfunctionwithanactiverealarmsystem.
Closed: Normal function.
Open: Emergency opening of the door.
BUTTON: No function.
LB / SKS: No function.
STOP: Interruption of the emergency opening for the duration of activation.
No automatic closing after deactivation of the BMA signal.
MOD10 Button ventilation function NO Sect. opening of the door. By pressing an additional button at input 1, the intermediate CLOSED position
(Sect. CLOSED) is approached from both directions, independent of the current door position.
MOD11 “Automaticclosing”button 1. Actuation: No automatic closing, open time is stopped.
2. Actuation: Automatic closing is active again if open time > 0.
3. Actuation: No automatic closing, open time is stopped.
…
MOD12 Laser scanner (height detection) Only in conjunction with input 2 (MOD6).
Ô See explanations for input 2