46 – Control CS 320 / Rev.D 1.01
H. Input-dependent messages
MOD Description Remarks
MOD32 Battery operation Active with battery operation. Input 2 is bridged (setting MOD5).
MOD33 no battery operation Active with mains operation. Input 2 is open (setting MOD5).
When programmed with MOD32/33, the relays operate as delayed changeover contacts and follow the
signal at input 2 when MOD5 is set.
In this case, input 2 is fed with a control signal from the UPS system, which ensures the changeover
between mains supply and UPS supply.
MOD34 BMA signal Switcheswithanactiverealarmsystem.
Follows the signal at input 1 with setting MOD5-9 / 13.
Inthiscase,input1isfedwithacontrolsignalfromtherealarmsystemand,dependingonthesetting,
the door opens or closes to an end or intermediate position.
I. System messages
MOD Description Remarks
MOD31 Service The relay is active after reaching the programmed service interval. Only after the service interval is reset or
redeneddoestherelaydropoutagain.
Ô “10.2Inputoperatingmode”onpage35
MOD46 ADJUSTMENT operating mode The relay is active if the control is in the ADJUSTMENT operating mode.
10.4 10.4 Explanations of the inputs:Explanations of the inputs:
A. Functions input 1
MOD Description Remarks
MOD1 SECT. OPEN button By pressing the button (input 1), the door opens to the intermediate OPEN position (SECT. OPEN).
MOD2 SECT. OPEN switch Closed: All OPEN commands lead to intermediate OPEN position (SECT. OPEN).
Open: All OPEN commands lead to the OPEN limit position.
MOD3 AUT.CLOSE switch Closed: No automatic closing.
(Open time stops, if open time > 0).
Open: Automatic closing is active (if open time > 0).
MOD4 External CLOCK (permanent OPEN) The door opens as soon as the contact closes and remains in the OPEN position (maintain open time)
until the contact opens. Then the door drives closed automatically (only with open time > 0). This function
can be cancelled by actuating the CLOSE button. The door drives CLOSED.
Functional overviews