Control CS 320 / Rev.D 1.01 – 45
F. Movement signal
MOD Description Remarks
MOD29 Door drives open. Active with movement in the OPEN direction.
MOD30 Door drives closed. Active with movement in the CLOSE direction.
MOD43 Door drives open or closed. Active with all movement.
The brake monitoring module BWM 1 is not active with this setting!
G. Functions for external accessories
MOD Description Remarks
MOD13 Magnetic lock function The relay closes before every door movement. The relay is opened in the standby position.
A delay time of 0.5 seconds is set before every door movement.
MOD21 Test of the trap-in protection The relay generates a test signal upon reaching the CLOSED limit position and awaits actuation of the
STOP circuit as a response to the test signal.
MOD22 Activation of transmission system
radio 1 and radio 4,
test of light grid 1
The relay generates a test signal upon reaching the OPEN limit position and awaits actuation of the
switching strip input as a response to the test signal.
MOD24 Capacitor switching With every operation command, the relay is closed for approx. 1 second. This relay is used to add an
additional start capacitor required for alternating current applications to ensure safe starting of the motor.
For series STAW with increased switch-on duration.
MOD25 Courtyard light function With each OPEN command, the relay is closed for 2 minutes and can therefore be used to control a
lighting system.
MOD26 Activation of transmission system
radio 2 and radio 4
Before every DOWN command, the transmission system radio is activated with a pulse. The duration of
activation must be set on the transmission system.
As a result of this activation, travel is delayed by approx. 0.5 seconds.
MOD28 Relay OFF The relay is switched off as a general rule, the contact is always open.
MOD36 Pneumatic cylinder for locking
the slip door (threshold-free door
system)
With every OPEN command the relay is activated and controls a pneumatic cylinder that mechanically
locks the slip door of the door. The locking position of the cylinder is queried via a limit switch. Only after
this limit switch is released does the door start to move. The relay remains active until the lower end point
is reached again.
MOD37 Testing the stop signal via
transmission system radio 1 and
radio 3
The relay generates a test signal upon reaching the OPEN limit position and awaits an interruption of the
stop circuit as a response to the test signal.
MOD38 Testoflightgrid2(8.2kΩ),
connection via input 2 (X4 /
11+12)
The relay generates a test signal upon reaching the OPEN limit position and awaits an interruption at
input 2 as a response to the test signal.
MOD 41 Activation transmission system
radio 4 in OPEN direction
The relay generates a test signal upon reaching the CLOSED limit position and awaits an interruption at
input 2 as a response to the test signal.
MOD49 Testing presence and movement
sensors (NC)
The relay generates a test signal each time before closing travel and awaits an interruption of the closing
edge input as a response to the test signal.