44 – Control CS 320 / Rev.D 1.01
C. Pulse signals
MOD Description Remarks
MOD4 Pulse with OPEN command from inside The relay closes the contact for 1 second if the door receives an OPEN command from inside.
It is possible to realise light actuation with this pulse for example.
MOD27 Pulse after reaching the OPEN limit
position
The relay closes the contact for 2 seconds if the door reaches the OPEN limit position.
It is possible to open a downstream cabinet with this pulse for example.
MOD 40 Pulse with OPEN command from outside The relay closes the contact for 1 second if the door receives an OPEN command from outside.
It is possible to realise light actuation with this pulse for example.
D. Brake functions (can only be set at relay 4)
MOD Description Remarks
MOD14 Brake (closed-circuit current
principle)
Theswitchingcontactofthebrakerectieriscontrolledviatherelayinordertoimplementafaster
braking function. As soon as the door moves, the contact is closed and the brake is vented (closed-circuit
current principle).
MOD15 Brake (open-circuit current
principle)
Theswitchingcontactofthebrakerectieriscontrolledviatherelayinordertoimplementafaster
braking function. As soon as the door moves, the contact is opened and the brake is vented (open-circuit
current principle).
MOD16 Brake (closed-circuit current
principle) applied in OPEN limit
position
Theswitchingcontactofthebrakerectieriscontrolledviatherelayinordertoimplementafaster
braking function. As soon as the door moves, the contact is closed and the brake is vented (closed-circuit
current principle). To achieve a smoother stopping behaviour of the door in the top limit position, the
switching contact is not switched in the OPEN LIMIT POSITION.
E. Error messages
MOD Description Remarks
MOD5 Fault message The relay opens the contact if a STOP command or an error is present.
All errors of chapter 11 lead to relay actuation.
MOD17 Closing edge protective device SKS
1-4 actuated
Monitoring SKS1 (X4/5-8) , SKS2 (X4/11-12) and SKS3/SKS4 (transmission system).
The relay opens the contact if one of the closing edge protective devices SKS 1-4 is actuated.
An error with one of the closing edge protective devices or a faulty test is displayed via MOD5.
MOD35 Light barrier Analogous to the light barrier input X4 (3/4), switches the applied signal on as a message.
Relay ON: Light barrier signal is OK
Relay OFF: Light beam interrupted or light barrier defective
MOD39 Error LED The relay always closes the contact if the internal error LED 2 (red) lights up.
MOD45 Closing edge protective devices
SKS 1-4 OK
Monitoring SKS1 (X4/5-8) , SKS2 (X4/11-12) and SKS3/SKS4 (transmission system)
Relay ON: All closing edge protective devices are OK
Relay OFF: At least one closing edge protective device is actuated or defective
Functional overviews