6 – Control CS 320 / Rev.D 1.01 Control CS 320 / Rev.D 1.01 – 7
EN
Detailed wiring diagram of mains connection and
motor connection (230 V / 3-phase)
B2
B1
W
V
U
N
L3
L2
L1
X1
X21
F2.1
F2.2
F2.3
F1
X19
X11
X18
X2
M
3
3
230 V / 50 Hz
/ PE
5.2 / 2
Detailed wiring diagram of mains connection and
motor connection (230 V / 1-phase)
B2
B1
AUF
ZU
N
L
N
X1
X21
F2.1
F2.2
F2.3
F1
X19
X11
X18
X2
M
1
1
230 V / 50 Hz
/ N / PE
5.2 / 3
Explanation:
M1: Motor
X1: Mains connection terminal strip
X2: Motor terminal strip
X11: Connector strip for electronic limit position system
(AWG) with safety circuit
X15: Terminal strip for mechanical limit switches (MEC)
(safety circuit to X2 / B1-B2)
X19: Connection for supplying external devices
Connection:
Connect electronic limit position system (AWG) or Connect electronic limit position system (AWG) or
mechanical limit switch (MEC) to the controller.mechanical limit switch (MEC) to the controller.
Connect controller to the motor.Connect controller to the motor.
Connect controller to the mains network. Connect controller to the mains network.
Secure cable groups with a cable tie directly before the Secure cable groups with a cable tie directly before the
respective terminal.respective terminal.
Check and compare technical data.Check and compare technical data.
Ô “12.Technicaldata”
5.3 5.3 Internal fuse protectionInternal fuse protection
ThecontrollerCS320isequippedwithinternalfuse
protection (F2) at the mains input. The fuse elements are
equippedwithnefuses8A/T(5.2x20mm)inthefactory.
N
L3
L2
L1
X1
X21
F2.1
F2.2
F2.3
3
400 V / 50 Hz
/ N / PE
5.3 / 1
ATTENTION!
Malfunctions due to improper fuse protection of
the controller!
Internal fuse maximum 10 A / T!
The internal fuses do not replace fuse protection of the
supply cable. This shall be realised with max. 16 A and must
beconguredastripleblockcircuitbreakersoftypeC.
Ô “5.2Mainsconnection”