38 – Control CS 320 / Rev.D 1.01
Function Description
Adjustment
options
Factory setting
REVERSE OFF Reversing point. Point at which the reversing of the door is switched off.
Only appears with systems with an electronic limit position system (AWG). Setting in
increments, starting from bottom limit switch-off point. In the case of systems with
mechanical limit switches, the supplementary limit switch DOWN serves as reversing
point.
A (teaching)
1 – 1000
50
LIGHTBARR.1 Light barrier 1, with or without testing, mounted in passage area of the door.
Connection to X4 / 1-4. The respective system connected is automatically detected and
taught.
Ô Wiringdiagrams“5.10Connectionofclosingedgeprotectivedevice1”onpage15
MOD1: 2-wire-system (Marantec Legden) with testing
MOD2: 3-wire-system NPN without testing
MOD3: 3-wire-system PNP without testing
4-wire-system NC contact without testing
MOD4: 3-wire-system NPN with testing
MOD5: 3-wire-system PNP with testing
4-wire-system NC contact with testing
NOTE:
Ifa3-or4-wire-systemisoperatedwithtesting,therespectiveMOD(4or5)mustbe
set manually.
A (teaching)
MOD1 – MOD5
A
LB FUNC. 1 Function of the light barrier 1 in passage area of the door.
DOWN door movement UP door movement
MOD1: Stop + reversing No action
MOD2: Stop + rev No action
MOD3: STOP No action
MOD4: STOP STOP
MOD5: Stop + reversing Ride-along suppression
(UP door movement only possible if
the light barrier is clear).
MOD6: No action Stop + reversing
MOD7: No action Stop + rev
MOD8: No action Stop
MOD9: Ride-along suppression Stop + reversing
(DOWN door movement only possible,
if the light barrier is clear).
MOD1 – MOD9 MOD1
LB FUNC. 2 Function of the light barrier 2 in passage area of the door.
Only appears when setting parameter INPUT 1 = MOD15.
Connection only as NC contact via programmable input 1 (X4 / 9+10).
Selection mode analogous to the settings under LB FUNC. 1
MOD1 – MOD9 MOD1
LB POINT Between limit position DOWN and LB POINT, the light barrier 1 (X4 / 1-4) is not
evaluated. Setting in increments, starting from bottom limit switch-off point.
Onlyappearswithsystemswithanelectroniclimitswitch.
Note: Attherstapproachduringadjustment,thispointisautomaticallydetected,
provided that light barrier 1 is mounted in the door frame and remains interrupted
during the downward travel from this point to the limit position DOWN.
A (teaching)
1–UPSWITCH
A
IMPULS Selection of a function that should be assigned to the impuls button (X3 / 7+8).
MOD1: UP-STOP-DOWN-STOP-UP…(sequentialcontrol)
MOD2: UP when door is stationary / no action during UP movement
Stop and run open with DOWN movement
MOD3: UP when door is stationary / STOP with door movement
MOD4: UP when door is stationary / no action with door movement
MOD5: UP when door is stationary / DOWN from UP limit position
MOD1 – MOD5 MOD1