Control CS 320 / Rev.D 1.01 – 37
Function Description
Adjustment
options
Factory setting
MOD37: Testing stop signal transmission system radio 1 and 3
MOD38: Testing light grid 2 (input 2)
MOD39: Error LED
MOD40: Pulse signal with UP command from outside
MOD41: Test transmission system radio 4 in UP direction
MOD43: Drive moving
MOD44: (Redtrafclightinside+outside)
. . . . .DOWNdoormovementfromintermediatepositionDOWN-ashing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UP door movement - off
MOD45: Closing edge in function
MOD46: Controller in operating mode ADJUSTMENT
MOD49: Testing presence and movement sensors (NC)
MOD60:
(Redtrafclightoutside1)forewarning-ashing,doorrunning-illuminated
MOD61: (Redtrafclightoutside2)forewarning-ashing,doorrunning-ashing
MOD62:
(Greentrafclightoutside)limitpositionUP-illuminated,forewarning/door
running - off
TL REST Switchtrafclights
MOD1: off in standby position
MOD2: on in standby position
MOD3: off after 5 minutes when in standby position
MOD1 – MOD3 MOD1
SKS MOD1: OSE (photo sensor)
MOD2: 8.2kΩ(electriccontactstrip)
MOD3: DW (pressure wave strip) as NC with testing
MOD4: Light grid OSE without testing
MOD5: Light grid SSR or PNP with testing
MOD6: Light grid SSR or PNP without testing
MOD7: 2-wire OSE (photo sensor with 2 connection wires)
NOTE:
MOD4, MOD5 and MOD6 must be set manually when using a light grid.
– Without addition of the open time (if programmed) after interruption of the light
grid during the automatic closing.
– Withoutswitch-offofthefunction“Automaticclosing”after3interruptionsin
succession.
A (teaching)
MOD1 – MOD7
A
DW TEST Activation and deactivation of the test function for the connected pressure wave strip.
Only appears when setting parameter SKS = MOD3.
MOD1: Test OFF
MOD2: Test ON
MOD1 – MOD2 MOD2
DW-POINT Point at which the connected pressure wave strip (X4 / 5+6) is tested.
Only appears when setting parameter SKS = MOD3.
Setting in increments (only AWG), starting from bottom limit switch-off point.
In the case of systems with mechanical limit switches, the supplementary limit switch
DOWN serves as a DW-Point.
0 – 1000 20
SKS FUNC. MOD1: Stop + reversing
MOD2 Stop + rev for 2 seconds
MOD1 – MOD2 MOD1
SKS REV MOD1: Stop + reversing betw
een limit position UP and reversing point
Stop between reversing point and limit position DOWN
➜ for vertically closing doors
MOD2 Stop + reversing betw
een limit position UP reversing point
No action between reversing point and limit position DOWN
➜ for vertically closing doors with leading light barrier
MOD3: Stop + reversing between limit position UP and limit position DOWN
➜ for horizontally closing doors and systems with mechanical limit
switches without pre-limit switch
NOTE:
In the case of systems with mechanical limit switches the supplementary limit switch
DOWN serves as reversing point.
MOD1 – MOD3 MOD1