56 – Control CS 320 / Rev.D 1.01
Fault / message LED display Remarks
ERROR RUNTIME 6xashing The programed running time has been exceeded.
– Check the path of the door and running time.
– Re-programme the running time if necessary.
ERROR MSBUS 9xashing Communication error between the controller and connected
MS-BUS end device.
– Check cable and connector and replace if necessary.
SERVICE 10xashing The programmed service interval has been reached.
– Resetorredeneserviceinterval.
Ô “10.2Inputoperatingmode”/SERVICEparameter
ERROR POWERSEGM. 11xashing The load contactor or a relay is defective.
– The circuit board must be replaced.
ERROR STOP Continuous illumination,
travel no longer possible.
– An error has occurred at the safety input
(X4/11-12 - MOD2).
– Check all components at the safety input and replace if
necessary.
ERROR SKS Continuous illumination,
travel only in dead man’s function.
Closing edge protective device faulty in OPEN or CLOSE
direction.
– Check closing edge protective devices and spiral cable,
if nec. check transmission system RADIO.
ERRORLIGHTBAR. Continuous illumination,
Travel in CLOSE direction only in dead man’s
function.
The connected light barrier exhibits a permanent fault.
– Check light barrier (function and alignment).
– Check cabling.
Fault display and remedial measures