EasyManua.ls Logo

Mecademic Meca500 - Power Status

Mecademic Meca500
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual for the Meca500 Industrial Robot (for rmware 10.1) 47
OPERATING THE SMART POWER SUPPLY
ResetA (7)
Reset – K (15)
External reset
Inside power supply
R
V
in
5 V ≤ V
in
≤ 24 V
R = V
in
/ 0.024
P
res ≥
V
in
²
/ R
Inside power supply
V
in
5 V ≤ V
in
≤ 24 V
ResetA (7)
Reset – K (15)
External reset
current
limiter
(a) Wiring the external reset in the Meca500 R3 (b) Wiring the external reset in the Meca500 R4
Figure30: Examples of wiring the external reset in the Meca500 R3 and R4
!
In the Meca500 R3, YOU MUST USE RESISTANCES to limit to current applied to the external reset
terminals to 24mA, or else you will damage the power supply.
7.3.5 Power Status
The power status terminals provide an output signal that corresponds to the power state of the robot
(in the case of R3) or of the robot motors (in the case of R4). The current on these terminals is limited to
60mA, and the voltage to 24 V (DC). There is no difference between the R3 and R4 with regards to the
power status connection.
Two examples of wiring the power status terminals are given in Figure31.
!
In both the R3 and R4 versions of the Meca500, the maximum voltage applied at the power
status terminals must be 24 V (DC), and the maximum current must be limited to 60 mA.

Table of Contents