MI 3125 / BT EurotestCOMBO Measurements
41
Displayed results:
I ........... Trip-out current,
Uci Contact voltage at trip-out current I or end value in case the RCD didn’t
trip,
t ........... Trip-out time.
5.4.4 RCD Autotest
RCD autotest function is intended to perform a complete RCD test (trip-out time at
different residual currents, trip-out current and contact voltage) in one set of automatic
tests, guided by the instrument.
Additional key:
Toggles between top and bottom part of results field.
RCD autotest procedure
* model MI 3125 BT
Select the RCD function using the function selector switch.
Set test parameters (if necessary).
Connect test cable to the instrument.
Connect test leads to the item to be tested (see figure
5.17).
Press the TEST key to perform the test.
Test with I
N
, 0 (step 1).
Test with I
N
, 180 (step 2).
Test with 5I
N
, 0 (step 3).
Test with 5I
N
, 180 (step 4).
Test with ½IN, 0 (step 5).
Test with ½IN, 180 (step 6).
Trip-out current test, 0 (step 7).
Trip-out current test, 180 (step 8).
Store the result by pressing the MEM key (optional)*.