MI 3125 / BT EurotestCOMBO Measurements
39
RCD type
Contact voltage Uc
proportional to
Rated I
N
AC
1.05I
N
any
All models
AC
S
21.05I
N
A, F
1.41.05I
N
30 mA
A, F
S
21.41.05I
N
A, F
21.05I
N
< 30 mA
A, F
S
221.05I
N
B, B+
21.05I
N
any
Model MI 3125 BT
B, B+
S
221.05I
N
Table 5.1: Relationship between Uc and I
N
Loop resistance is indicative and calculated from Uc result (without additional
proportional factors) according to:
N
C
L
I
U
R
.
Figure 5.18: Example of contact voltage measurement results
Displayed results:
Uc ........ Contact voltage.
Rl ......... Fault loop resistance.
5.4.2 Trip-out time (RCDt)
Trip-out time measurement verifies the sensitivity of the RCD at different residual
currents.
Trip-out time measurement procedure
* model MI 3125 BT
Select the RCD function using the function selector switch.
Set sub-function RCDt.
Set test parameters (if necessary).
Connect test cable to the instrument.
Connect test leads to the item to be tested (see figure 5.17).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional)*.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL EurotestCOMBO MI 3125 and is the answer not in the manual?

METREL EurotestCOMBO MI 3125 Specifications

General IconGeneral
BrandMETREL
ModelEurotestCOMBO MI 3125
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals