MI 3125 / BT EurotestCOMBO Measurements
39
Contact voltage Uc
proportional to
Table 5.1: Relationship between Uc and I
N
Loop resistance is indicative and calculated from Uc result (without additional
proportional factors) according to:
.
Figure 5.18: Example of contact voltage measurement results
Displayed results:
Uc ........ Contact voltage.
Rl ......... Fault loop resistance.
5.4.2 Trip-out time (RCDt)
Trip-out time measurement verifies the sensitivity of the RCD at different residual
currents.
Trip-out time measurement procedure
* model MI 3125 BT
Select the RCD function using the function selector switch.
Set sub-function RCDt.
Set test parameters (if necessary).
Connect test cable to the instrument.
Connect test leads to the item to be tested (see figure 5.17).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional)*.