MI 3125 / BT EurotestCOMBO Appendix C
79
C.2.1.1 Modification of Appendix A
In addition to fuse data given in Appendix A gR fuses are added.
Fuse type gR
Rated
current
(A)
Disconnection time [s]
35m
0.1
0.2
0.4
5
Min. prospective short- circuit current (A)
2
31.4
14
10
8
5
4
62.8
28
20
16
10
6
94.2
42
30
24
15
10
157
70
50
40
25
13
204
91
65
52
32.5
16
251
112
80
64
40
20
314
140
100
80
50
25
393
175
125
100
62.5
32
502
224
160
128
80
35
550
245
175
140
87.5
40
628
280
200
160
100
50
785
350
250
200
125
63
989
441
315
252
157.5
80
1256
560
400
320
200
100
1570
700
500
400
250
125
1963
875
625
500
313
160
2510
1120
800
640
400
200
3140
1400
1000
800
500
250
3930
1750
1250
1000
625
315
4950
2210
1575
1260
788
400
6280
2800
2000
1600
1000
500
7850
3500
2500
2000
1250
630
9890
4410
3150
2520
1575
710
11150
4970
3550
2840
1775
800
12560
5600
4000
3200
2000
1000
15700
7000
5000
4000
2500
1250
19630
8750
6250
5000
3130
C.2.2 AT modification - G type RCD
Modified is the following related to the mentioned in the chapter 5.4:
- Added G type RCD,
- Time limits are the same as for general type RCD,
- Contact voltage is calculated the same as for general type RCD.
Modifications of the chapter 5.4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL EurotestCOMBO MI 3125 and is the answer not in the manual?

METREL EurotestCOMBO MI 3125 Specifications

General IconGeneral
BrandMETREL
ModelEurotestCOMBO MI 3125
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals