MI 3125 / BT EurotestCOMBO Technical specifications
68
9.3.4 Trip-out current
Trip-out current
Complete measurement range corresponds to EN 61557 requirements.
Measuring range I
Resolution I
Accuracy
0.2I
N
1.1I
N
(AC type)
0.05I
N
0.1I
N
0.2I
N
1.5I
N
(A, F types, I
N
≥30 mA)
0.05I
N
0.1I
N
0.2I
N
2.2I
N
(A, F types, I
N
<30 mA)
0.05I
N
0.1I
N
0.2I
N
2.2I
N
(B, B+ types)*
0.05I
N
0.1I
N
Trip-out time
Measuring range (ms)
Resolution (ms)
Accuracy
0 300
1
3 ms
Contact voltage
Measuring range (V)
Resolution (V)
Accuracy
0.0 19.9
0.1
(-0 % / +15 %) of reading 10 digits
20.0 99.9
0.1
(-0 % / +15 %) of reading
The accuracy is valid if mains voltage is stabile during the measurement and PE
terminal is free of interfering voltages.
Trip-out measurement is not available for I
N
=1000 mA (RCD types B, B+)*.
Specified accuracy is valid for complete operating range.
9.4 Fault loop impedance and prospective fault current
9.4.1 No disconnecting device or FUSE selected
Fault loop impedance
Measuring range according to EN61557 is 0.25 9.99k.
Measuring range ()
Resolution ()
Accuracy
0.00 9.99
0.01
(5 % of reading + 5 digits)
10.0 99.9
0.1
100 999
1
10 % of reading
1.00k 9.99k
10
Prospective fault current (calculated value)
Measuring range (A)
Resolution (A)
Accuracy
0.00 9.99
0.01
Consider accuracy of fault
loop resistance
measurement
10.0 99.9
0.1
100 999
1
1.00k 9.99k
10
10.0k 23.0k
100
The accuracy is valid if mains voltage is stabile during the measurement.
Test current (at 230 V) ...................... 6.5 A (10 ms)
Nominal voltage range ....................... 93 V 134 V (45 Hz 65 Hz)
185 V 266 V (45 Hz 65 Hz)