A.2 Fuse table Impedances at 230 V a.c. (AS/NZS 3017)
Type B
Type C
Rated
current
(A)
Disconnection time [s]
Rated
current
(A)
Disconnection time [s]
0.4
0.4
Max. loop impedance ()
Max. loop impedance ()
6
9.58
6
5.11
10
5.75
10
3.07
16
3.59
16
1.92
20
2.88
20
1.53
25
2.30
25
1.23
32
1.80
32
0.96
40
1.44
40
0.77
50
1.15
50
0.61
63
0.91
63
0.49
80
0.72
80
0.38
100
0.58
100
0.31
125
0.46
125
0.25
160
0.36
160
0.19
200
0.29
200
0.15
Type D
Fuse
Rated
current
(A)
Disconnection time [s]
Rated
current
(A)
Disconnection time [s]
0.4
0.4
5
Max. loop impedance ()
Max. loop impedance ()
6
3.07
6
11.50
15.33
10
1.84
10
6.39
9.20
16
1.15
16
3.07
5.00
20
0.92
20
2.09
3.59
25
0.74
25
1.64
2.71
32
0.58
32
1.28
2.19
40
0.46
40
0.96
1.64
50
0.37
50
0.72
1.28
63
0.29
63
0.55
0.94
80
0.23
80
0.38
0.68
100
0.18
100
0.27
0.48
125
0.15
125
0.21
0.43
160
0.12
160
0.16
0.30
200
0.09
200
0.13
0.23
All impedances are scaled with factor 1.00.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL EurotestCOMBO MI 3125 and is the answer not in the manual?

METREL EurotestCOMBO MI 3125 Specifications

General IconGeneral
BrandMETREL
ModelEurotestCOMBO MI 3125
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals