LEVEL SYSTEM SYNCHRONIZATION
When multiple ultrasonic level monitors are installed within a single plant/facility,
ensure the transducer cable(s) of each system are run in separate grounded metal
conduits. Otherwise, synchronize the level monitors.
When level monitors are synchronized, no unit can transmit while another is awaiting
echo reception.
To synchronize the HYDRO+ with a DPL+, XPL+, and/or another HYDRO+...
1. Mount the level monitors together in one cabinet.
2. Use a common power (mains) supply and ground (earth) for all units.
3. Interconnect the SYNC terminals of all level monitors.
To synchronize the HYDRO+ with other Milltronics
ultrasonic level monitors contact Milltronics
or your local distributor.
HYDRO +
# 1
HYDRO +
# 2
to next
device
Wall Mount
HYDRO +
# 1
HYDRO +
# 2
Rack or Panel Mount
INSTALLATION
PL-507 23