QX-5000 Series Installation and Operation Manual
47
All-Call Minus Button
Inverts the selection of zones for voice paging. This button will not function if DIP switch SW1-5 Automatic All-Call is
set to ON.
Microphone PTT Button
The microphone's PTT (push-to-talk) button, when depressed, causes voice paging (from the microphone) to be
enabled to all zones selected for paging, unless page inhibit is active. Note that pressing PTT will not result in any
paging activity unless there are zones selected for paging.
Warden Page Button
When depressed, the Warden Page button enables voice paging from the firefighters' telephone (if connected) to all
zones selected for paging, unless page inhibit is active. Note that pressing PTT will not result in any paging activity
unless there are zones selected for paging. Also note that there must be an active firefighters' telephone connection
for warden paging to occur.
QZP-5101 Displays
Page LED
Illuminates green if the zone is selected for voice paging.
Evac LED (if enabled)
Alienates red if the zone is selected for evacuation.
Trouble LED
Flashes amber to indicate that the zone is in trouble.
QZP-5101 Switches
Page Button (if enabled)
Selects / deselects that zone for voice paging.
Evac Button
Selects only that zone for evacuation.