QX-5000 Series Installation and Operation Manual
3
Introduction
About this Manual
This installation and operation manual provides information on installing the QX-5000 Series Emergency Zoned &
Firefighters’ Telephone System.
About the QX-5000
Mircom's QX-5000 Emergency Zoned Audio & Firefighters’ Telephone System is a zoned emergency multi-channel
audio system, providing emergency paging and fire evacuation, and optional firefighters’ telephone communication
to and from the central lobby location to all remote telephone handsets. The system consists of an audio cabinet
(usually intended for electrical room installation) which contains a motherboard and card cage which holds up to 7
amplifiers and interface board. The system also includes a audio power supply, battery charger and batteries all
housed in an audio backbox enclosure.
For communication and annunciation there is a microphone for paging, a paging selector panel, firefighters’
telephone and associated selector panels all housed in a lobby enclosure. The paging and telephone modules are
usually intended for installation in a central lobby.
Note that the paging and firefighters’ telephone may be used together or independently, connected to a Fire Alarm
Control Panel.
Overall Features:
UL and ULC listed
Supervises signal circuits while in use
Control of fire management operations (e.g. all-call paging and total evacuation signalling)
Indications of all required fault conditions
Microprocessor-based operations with hardware and software watchdog timer to ensure reliable system
operation
Supervised tone generators
Up to 144 audio zones with paging controls, or 72 audio zones with both paging & evacuation controls
Up to 60 firefighters’ telephone zones
Easy configuration process
Operates from 24 VDC backup batteries in the event of a power failure
Removable terminal blocks for ease of installation and maintenance
Speaker circuits integrated with amplifier circuits
Multiple amplifier sizes (up to 7 per audio cabinet, MAXIMUM 360 Watts per cabinet)
Optional redundant backup amplifier
Multiple audio cabinets may be interconnected (up to a maximum of eight audio cabinets)
Technical Support
For all technical support inquiries, please contact Mircom’s Technical Support Department between 8 A.M. and 5
P.M. (EDT) Monday through Friday, excluding holidays.
Local Phone: 905-660-4655 Toll-Free Phone: 1-888-660-4655
Local Fax: 905-660-4113 Toll-Free Fax: 1-888-660-4113
E-mail: techsupport@mircom.com

Table of Contents

Other manuals for Mircom QX-5000 Series

Related product manuals