A.1.1 PLC Status Diagnostic Information (M8000 to M8009)
A.1.2 Clock Devices and Real Time Clock (M8011 to M8019)
Special Relays Appendix
A-2 MITSUBISHI ELECTRIC
RUN state
M8004
M8000
M8001
M8002
M8003
1 scan time
Special Relay Read Write CPU Function
M8000
FX
1S
FX1N
FX2N
FX2NC
FX3G
FX3U
FX3UC
RUN monitor
(NO contact)
M8001
RUN monitor
(NC contact)
M8002
Initial pulse
(NO contact)
M8003
Initial pulse
(NC contact)
M8004
Error occurrence
M8005
FX
2N
FX2NC
FX3G
FX3U
FX3UC
Battery voltage low (ON when battery voltage is below the
value set in D8006)
M8006
Battery error latch (M8006 is set when battery voltage low is
detected)
M8007
—FX
2N
FX2NC
FX3U
FX3UC
Momentary power failure
M8008
Power failure detected
M8009
FX
2N
FX2NC
FX3G
FX3U
FX3UC
24V DC down (service power supply)
Special Relay Read Write CPU Function
M8010 Not used
M8011
FX
1S
FX1N
FX2N
FX2NC
FX3G
FX3U
FX3UC
10 ms clock pulse
ON and OFF in 10 ms cycle (ON: 5 ms, OFF: 5 ms)
M8012
100 ms clock pulse
ON and OFF in 100 ms cycle (ON: 50 ms, OFF: 50 ms)
M8013
1 s clock pulse
ON and OFF in 1 s cycle (ON: 500 ms, OFF: 500 ms)
M8014
1 min clock pulse
ON and OFF in 1 min cycle (ON: 30 s, OFF: 30 s)
M8015
쏹쏹
Clock stop and preset (For real time clock)
M8016
Time read display is stopped (For real time clock)
The contents of D8013 to D8019 is frozen, but the clock is
still running.
M8017
쏹쏹
±30 seconds correction (For real time clock)
M8018
Real time clock installation detection (Always ON)
For an FX
2NC a memory card with integrated RTC must be
installed.
M8019
Real time clock (RTC) setting error