A.4.4 Special Function Modules
햲
When analog special function blocks (FX0N-3A, FX2N-2AD and FX2N-2DA) are connected to an input/ output po
-
wered extension unit (FX
2N-32E첸 or FX2N-48E첸 ), the following limitation must be taken into consideration.
(When the blocks are connected to the base unit, this limitation is not applied.)
The total current consumption of the analog special function blocks (FX
0N-3A, FX2N-2AD and FX2N-2DA) should
be less than the following current values.
- When connected to FX
2N-32E첸: 190 mA or less
- When connected to FX2N-48E첸: 300 mA or less.
햳
When the voltage of the external DC power supply is 5 V DC, the current is 100 mA.
햴
AFX2N-16CCL-M cannot be used together with a FX2N-32ASI-M.The following number of points is added accord
-
ing to the products connected to the network: (Number of remote I/O stations) x 32 points.
햵
AFX2N-32ASI-M cannot be used together with a FX2N-16CCL-M. Only one unit can be added to the whole sys
-
tem. The following number of points is added according to the products connected to the network:
(Number of active slaves) x 8 points.
NOTE When applying a DC power type base unit, calculate the current consumption at startup.
Number of Occupied Input/Output Points and Current Consumption Appendix
A-16 MITSUBISHI ELECTRIC
Type
Number of
occupied
I/O points
Current consumption [mA]
5 V DC 24 V DC (internal) 24 V DC (external) At start up
FX
3U-2HC 8 245 0 0 —
FX
3U-4AD 8 110 0 90 —
FX
3U-4DA 8 120 0 160 —
FX
3U-4LC 8 160 0 50 —
FX
3U-20SSC-H 8 100 0 220 —
FX
2N-2AD 8 20 50
0 170
FX
2N-2DA 8 30 85
0 190
FX
2N-4AD 8 30 0 55 —
FX
2N-4DA 8 30 0 200 —
FX
2N-4AD-TC 8 30 0 50 —
FX
2N-4AD-PT 8 30 0 50 —
FX
2N-8AD 8 50 0 80 —
FX
2N-5A 8 70 0 90 —
FX
2N-2LC 8 70 0 55 —
FX
2N-1HC 8 90 0 0 —
FX
2N-1PG-E 8 55 0 40 —
FX
2N-10PG 8 120 0 70
햳
—
FX
2N-232IF 8 40 0 80 —
FX
2N-16CCL-M 8
햴
0 0 150 —
FX
2N-32CCL-M 8 130 0 50 —
FX
2N-32ASI-M 8
햵
150 0 70 —
FX
0N-3A 8 30 90
0 165
FX
2N-10GM 8 — — 5 —
FX
2N-20GM 8 — — 10 —