EasyManua.ls Logo

Mitsubishi Electric FX Series - Error Codes (D8060 to D8069; Extension Boards

Mitsubishi Electric FX Series
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A.2.4 Error Codes (D8060 to D8069)
*
Cleared when PLC switches from STOP to RUN.
A.2.5 Extension Boards (Dedicated to FX1S and FX1N)
Special Registers Appendix
A-8 MITSUBISHI ELECTRIC
Special Register Read Write CPU Function
D8112
FX
1S
FX1N
Adapter FX1N-2AD-BD: Digital input value ch.1
D8113
Adapter FX
1N-2AD-BD: Digital input value ch.2
D8114
쏹쏹
Adapter FX
1N-1DA-BD: Digital output value ch.1
Special Register Read Write CPU Function
D8060
FX
2N
FX2NC
FX3G
FX3U
FX3UC
If the unit or block corresponding to a programmed I/O number
is not actually loaded, M8060 is set to ON and the first device
number of the erroneous block is written to D8060
Meaning of the four digit code:
1st digit: 0 = Output, 1 = Input
2nd to 4th digit: First device number of the erroneous block
D8061
FX
1S
FX1N
FX2N
FX2NC
FX3G
FX3U
FX3UC
Error code for PLC hardware error
D8062
FX
2N,
FX
2NC
FX3G
FX3U
FX3UC
Error code for PLC/PP communication error
FX
3G Error code for serial communication error [ch0]
D8063
FX
1S
FX1N
FX2N
FX2NC
FX3G
FX3U
FX3UC
Error code for serial communication error 1 [ch1]
D8064
Error code for parameter error
D8065
Error code for syntax error
D8066
Error code for ladder error
D8067
Error code for operation error
D8068*
Operation error step number latched
In case of 32K steps or more, the step number is stored in
[D8313, D8312].
D8069*
Error step number of M8065 to M8067
In case of 32K steps or more, the step number is stored in
[D8315, D8314].