M800VS/M80V Series Connection and Setup Manual
9 Connection of Operation Panel I/O Unit
9.7 Connecting with Manual Pulse Generator (MPG)
260
IB-1501613-A
9.7 Connecting with Manual Pulse Generator (MPG)
Connect the manual pulse generator to MPG connector of the operation panel I/O unit.
Both 5 V power supply type (UFO-01-2Z9) and 12 V power supply type (HD60C) manual pulse generator can be used. Take
the maximum cable length, etc. into consideration when selecting.
(1) Set one of the following parameters which is suitable for your manual pulse generator.
5 V manual pulse generator (UFO-01-2Z9): #1240 set12/bit0 = 1 (100 pulse/rev)
12 V manual pulse generator (HD60C): #1240 set12/bit0 = 0 (25 pulses/rev)
Connect the 5 V manual pulse generator to the connector MPG.
Connecting with 5 V manual pulse generator (maximum cable length: 20 m)
Note
MPG
NO.1
NO.1NO.2
NO.2NO.3 NO.1
5V0VAB
5V0VAB 5V0VAB
5V0VAB 5V0VAB 5V0VAB
J023
J024
J025
When connecting one 5V
manual pulse generator
When connecting two 5V
manual pulse generators
When connecting three
5V manual pulse
generators
Operation panel
I/O unit
5V manual pulse
generator
(Rear view)