Setting Parameters
09/01 AWB8230-1412GB
100
Parameter protection
The four following methods of parameter protection are available:
Magnetizing current
Set the magnetizing current with smaller motors or multiple-
motor operation accordingly.
PNU Name Adjustable in
RUN mode
Value Function WE
b31 Software
parameter
protection
– 00 Parameter protection through SFT input; all functions inhibited 01
01 Parameter protection through SFT input; input via PNU F01 possible
02 Parameter protection without SFT input; all functions inhibited
03 Parameter protection without SFT input; input via PNU F01 possible
PNU Name Adjustable in
RUN mode
Value Function WE
b32 Magnetizing
current
– 0 to 1.4 x I
e
1)
Setting range of the magnetizing current in multiples of the
inverter’s rated current
0.58 x I
e
1)
1) Inverter rated current