09/01 AWB8230-1412GB
116
Mains choke
Figure 99: DE4-LN... mains choke
h
When the frequency inverter is operating at its rated
current limit, the main choke causes a reduction of the
frequency inverter's greatest possible output voltage (U
2
)
to about 96 % of the mains voltage (U
LN
).
DF5- Mains
voltage
Mains current
(I
LN
) of the DF5
without mains
choke
Assigned
mains choke
322-018 1 ~ 230 V 3.1 DE4-LN1-037
322-037
5.8 DE4-LN1-037
322-055
6.7 DE4-LN1-075
322-075
9 DE4-LN1-1K5
322-1K1
11.2 DE4-LN1-1K5
322-1K5
16 DE4-LN1-2K2
322-2K2
22.5 DEK0,1-9,2
322-018 3 ~ 230 V
1.8 DE4-LN3-075
322-037
3.4 DE4-LN3-1K5
322-055
3.9 DE4-LN3-1K5
322-075
5.2 DE4-LN3-2K2
322-1K1
6.5 DE4-LN3-3K0
322-1K5
9.3 DE4-LN3-4K0
322-2K2
13 DE4-LN3-7K5
340-037 3 ~ 400 V
2 DE4-LN3-075
340-075
3.3 DE4-LN3-1K5
340-1K5
5 DE4-LN3-2K2
340-2K2
7 DE4-LN3-3K0
340-3K0
10 DE4-LN3-5K5
340-4K0
11 DE4-LN3-5K5
340-5K5
16.5 DE4-LN3-11K
340-7K5
20 DE4-LN3-11K
h
For technical data of the DE4-LN series mains choke, see
installation instructions AWA8240-1711.

Table of Contents