Setting Parameters
09/01 AWB8230-1412GB
80
Analog setpoint value matching
The external setpoint signal can be specifically matched with para-
meters PNU A11 to A16, which are described below. A configu-
rable voltage or current setpoint range can be assigned to a confi-
gurable frequency range.
Furthermore, analog setpoint signal filtering can be adjusted using
PNU A16.
Figure 77: Setpoint value matching
x: Voltage or current setpoint signal on analog input O or OI
PNU A11
0 V
PNU A13 PNU A14
10 V
4 mA 20 mA
PNU A12
PNU A15 = 00
PNU A15 = 01
f
[Hz]
PNU Name Adjustable in
RUN mode
Value Function WE
A11 Frequency with
minimum
setpoint value
0 to 360 Hz Here, the frequency that corresponds to the minimum voltage setpoint
value under PNU A13 is set.
0.0
A12 Frequency with
maximum
setpoint value
0 to 360 Hz Here, the frequency that corresponds to the maximum voltage setpoint
value under PNU A14 is set.
0.0
A13 Minimum
setpoint value
0 to 100 % The minimum setpoint value entered here relates to the maximum
possible voltage or current setpoint (10 V or 20 mA).
0
A14 Maximum
setpoint value
0 to 100 % The maximum setpoint value entered here relates to the maximum
possible voltage or current setpoint (10 V or 20 mA).
100
A15 Conditions for
start frequency
Determines the behaviour at setpoint values below the minimum setpoint value. 01
00 The frequency defined under PNU A11 is applied to the motor.
01 A frequency of 0 Hz is applied to the motor.
A16 Analog input
filter time
constant
To reduce the inverters response time to setpoint changes at the O or OI terminal, and
thereby determine the degree to which analog signal harmonics are filtered, you can enter
a value between 1 and 8 here.
8
1 Minimal filtering effect/fast response to setpoint value changes
....
8 Maximum filtering effect/slow response to setpoint value changes