09/01 AWB8230-1412GB
Frequency value messages
FA1/FA2
71
Overload message OL
The digital output configured as OL is activated when a freely
selectable motor current is exceeded. The OL output is active as
long as the motor current is higher than this threshold.
X If you want to configure a programmable digital output as OL,
you must set the current under PNU C41, at which the OL signal
activates when it has been exceeded.
X Then, program one or more of the digital outputs 11 or 12 as
the OL output, by setting the value 03 under PNU C21 or C22.
Figure 71: Digital output 11 configured as an OL overload
message
OL
24 V
50 mA
1112CM2
Figure 72: Function chart for OL Overload message
As the digital outputs 11 and 12 are configured as break contacts, OL
is active with 0.
OL
PNU C41
I
M
PNU Name Adjustable in
RUN mode
Value Function WE
C41 Overload alarm
threshold
0 to 2 x I
e
1)
The current value entered here determines when the OL over-
load signal should be activated.
I
e
1)
1) Frequency inverters rated current