Setting Parameters
09/01 AWB8230-1412GB
78
Setting the frequency and start command parameters
This section describes the methods for adjusting and setting the
start command and basic frequency-related parameters.
Definition of frequency setpoint value
With PNU A01, you set how the frequency setpoint value is to be
defined:
Via the potentiometer on the keypad
Via analog input O (0 to 10 V) or OI (4 to 20 mA)
Definition under PNU F01 and/or PNU A20
Start command
With PNU A02, you define whether the start command is issued
using the ON key of the keypad or through the digital inputs confi-
gured as FWD and REV.
PNU Name Adjustable in
RUN mode
Value Function WE
A01 Defined
frequency
setpoint
00 Definition with the potentiometer on the keypad 01
01 Definition via analog input O (0 to 10 V) or OI (4 to 20 mA)
02 Definition under PNU F01 and/or PNU A20
A20 Frequency
setpoint value
j 0.5 to 360 Hz You can input a frequency setpoint value. You must assign 02 under
PNU A01 for this purpose.
0.0
F01 Display/input
of frequency
value
j Display of the current frequency setpoint value or the current fixed
frequency.
Modified values are saved with the ENTER key according to the selection
of the digital inputs configured as FF1 to FF4 (a Section Fixed
frequency FF1 to FF4 selection, Page 56).
Resolution g0.1 Hz
PNU Name Adjustable in
RUN mode
Value Function WE
A02 Start command 01 The start command for starting the motor is issued by the digital inputs
configured as FWD or REV.
01
02 The start command for starting the motor is issued by the ON key on the
keypad.

Table of Contents