09/01 AWB8230-1412GB
UL
®
Caution, Warnings and
Instructions
125
UL
®
Caution, Warnings and Instructions
Preparation for Wiring
Determination of Wire and Fuse Sizes
The maximum motor currents in your application determines the
recommended wire size. The following table gives the wire size in
AWG. The Power Lines column applies to the inverter input
power, output wires to the motor, the earth ground connection,
and any other component. The Signal Lines column applies to
any wire connecting to the two green 7 and 8-position connectors
just inside the front enclosure panel.
C41 Threshold for overload alarm on digital output 11
and 12
I
e
C42 Frequency from which FA2 is switched on during
acceleration
0.0
C43 Frequency from which FA2 is switched off during
deceleration
0.0
C44 PID control deviation (in % of maximum setpoint value) 3.0
PNU Function WE Setpoint
Warning!
Use 60/75 °C Cu wire only or equivalent.
Warning!
Open Type Equipment.
Warning!
A Class 2 circuit wired with Class 1 wire or equivalent.
Warning!
Suitable for use on a circuit capable of delivering not
more than 5000 rms symmetrical amperes, 240 V
maximum. For models DF5-322.
Warning!
Suitabel for use on a circuit capable of delivering not
more than 5000 rms symmetrical amperes, 480 V
maximum. For models DF5-340.
DF5- Motor Output Wiring Applicable equipment
kW HP Power Lines Signal Lines Fuse (class J) rated 600 V
322-018 0.18 1/4 AWG16/1.3 mm
2
(*)
18 to 28 AWG/
0.14 to 0.75 mm
2
shielded wire
10 A
322-037
0.37 1/2
322-055
0.55 3/4
322-075
0.75 1 AWG14/2.1 mm
2
15 A
322-1K1
1.1 1 1/2 AWG14/2.1 mm
2
15 A
322-1K5
1.5 2 AWG12/3.3 mm
2
20 A (single ph.)
15 A (three ph.)
340-037
0.37 1/2 AWG16/1.3 mm
2
3 A
340-075
0.57 1 6 A
340-1K5
1.5 2 10 A
340-2K2
2.2 3 10 A
340-3K0
3.0 4 AWG14/2.1 mm
2
15 A
340-4K0
4.0 5 AWG14/2.1 mm
2
15 A
340-5K5
5.5 7 1/2 AWG12/3.3 mm
2
20 A
340-7K5
7.5 10 AWG12/3.3 mm
2
25 A
(*) Use 18 AWG/0.75 mm
2
wire for the alarm signal wire (K11, K12, K14 terminals).