Programming the control
signal terminals
09/01 AWB8230-1412GB
54
Programmable digital inputs 1 to 5
You can assign various functions to terminals 1 to 5. Depending
on your requirements, these terminals can be configured as
follows:
• clockwise start signal (FWD),
• anticlockwise start signal (REV),
• selection inputs for various fixed frequencies (FF1 to FF4),
• reset input (RST),
• etc.
The terminal function for each of the programmable digital inputs
1 to 5 occurs via PNU C01 to C05, i.e. you use PNU C01 to specify
the function of digital input 1, PNU C02 to specify the function of
digital input 2, etc. You cannot, however, assign the same function
to two inputs.
Programmable digital inputs 1 to 5 are configured as make
contacts by default. If, therefore, the function of an input terminal
is to be activated, the corresponding input must be closed (i.e. the
input terminal is connected to terminal P24). Conversely, to deac-
tivate the input terminal, the input must be opened.
Table 10: Digital inputs 1 to 5
A detailed description of the input functions can be found on the
pages listed in Table 11.
Tabelle 11: Functions of the digital inputs
If required, the digital inputs can be configured as break (NC)
contacts. For this purpose, under PNU C11 to C15 (corresponding
to digital inputs 1 to 5), 01 is to be input. An exception exists only
for inputs which you configure as RST (reset) or as PTC (PTC ther-
mistor input). These inputs can only be operated as make (NO)
contacts.
Table 12: Configuring digital inputs as break contacts
Caution!
If an EEPROM error occurs (fault message E08), all
parameters must be checked to ensure that they are
correct (particularly the RST input).
PNU Terminal Adjustable in
RUN mode
Value WE
C01 1 – a Table 11 00
C02 2
01
C03 3
02
C04 4
03
C05 5
18
Value Function Description a Page
00 FWD Start/stop clockwise 55
01 REV
Start/stop anticlockwise 55
02 FF1
First fixed frequency input 56
03 FF2
Second fixed frequency input
04 FF3
Third fixed frequency input
05 FF4
Fourth fixed frequency input
06 JOG
Jog mode 64
09 2CH
Second acceleration and
deceleration time
59
11 FRS
Motor shutdown and free
run stop
60
12 EXT
External fault 61
13 USP
Restart inhibit 62
15 SFT
Parameter protection 66
16 AT
Setpoint input through current 58
18 RST
Reset 63
19 PTC
PTC thermistor input
(digital input 5 only)
65
Caution!
If you reconfigure digital inputs configured as FWD or REV
as break contacts (the default setting is as a make
contact), the motor starts immediately. They should only
be reconfigured as break contacts when it is absolutely
essential.
PNU Termina
l
Valu
e
Adjustable in
RUN mode
Function WE
C11 1 00 or
01
– 00: Make
contact
01: Break
contact
00
C12 2
C13 3
C14 4
C15 5