Programming the control
signal terminals
09/01 AWB8230-1412GB
64
Jog mode (JOG)
When the digital input configured as JOG is activated, the motor
can be operated in jog mode. This mode is used, e.g. for manual
setting actions on machinery by issuing a start command on the
FWD or REV input with a relatively low frequency without applying
an acceleration ramp to the motor.
X Input under PNU A38 the frequency which is to be applied to
the motor when jog mode is active.
Make sure that the frequency is not too high, as it is applied
directly to the motor without an acceleration ramp. This could
cause a fault message to occur. Set a frequency below about 5 Hz.
X As the start command in jog mode is to be set via the FWD or
REV input, set under PNU A02 the value 01.
X Under PNU A39, you determine how the motor is to be braked.
X Program one of the digital inputs 1 to 5 as JOG, set the value
06 under the respective PNU (C01 to C05).
Figure 61: Digital input 1 configured as FWD (start/stop clockwise
rotation) and 3 as JOG (jog mode).
Figure 62: Function chart for JOG (jog mode)
n
M
:motor speed
a Depending on the setting of PNU A39
00: free run (coast)
01: deceleration ramp
02: DC braking
JOG
FWD
P2413
a
JOG
FWD/REV
n
M
a
Caution!
Make sure that the motor has stopped before using jog
mode.
PNU Name Adjustable in
RUN mode
Value Function WE
A02 Start command 01 The start command for starting the motor is issued by the digital inputs
configured as FWD or REV.
01
02 The start command for starting the motor is issued by the ON key on the
keypad.
A38 Frequency in
jog mode
j 0.5 to 9.99 Hz The frequency to be applied to the motor in jog mode. 1.0
A39 Type of motor
stop in jog
mode
00 Stop command on: the motor coasts to halt 00
01 Stop command on: the motor is braked to standstill using a deceleration
ramp
02 Stop command on: the motor is braked to standstill using DC braking
h
Jog mode cannot be applied if the value set for the jog
mode frequency under PNU A38 is less than the start
frequency set under PNU b82 (a Section RUN operati-
onal, Page 70)
h
Jog mode can only be activated when the frequency
inverter is in the Stop state.