Terminal Dimensions and Tightening Torque
The terminal screw dimensions for all DF5 inverters are listed in
Table 3 (a Page 30) and Table 5 (a Page 36). This information
is useful in sizing spade lug or ring lug connectors for wire
terminations.
When connecting wiring, use the tightening torque listed in the
above mentioned tables to safely attach wiring to the connectors.
h
Field wiring must be made by a UL-listed and CSA-
certified closed-loop terminal connector sized for the wire
gauge involved. Connector must be fixed by using the
crimping tool specified by the connector manufacturer.
h
Be sure to consider the capacity of the circuit-breaker
to be used.
h
Be sure to use larger wires for the power lines if the
distance exceeds 20 meters.
Warning!
When PNU b12 (level of electronic thermal setting) is set
to device FLA, device provides Solid State motor overload
protection at 115 % of device FLA or equivalent.
This PNU b12 (level of electronic thermal setting) is a
variable parameter (a Section ”Electronic motor protec-
tion”, Page 98).
Fuse (class J)
rated 600 V
UL Listed
Fuse (class J)
rated 600 V