EasyManua.ls Logo

Moeller DF5 series - Frequency and Start Command Settings

Moeller DF5 series
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
09/01 AWB8230-1412GB
75
6 Setting Parameters
The parameters listed in this section can be set using the keypad.
The adjustment and setting possibilities listed below are themati-
cally arranged according to their function. This provides a clear
overview of all parameters assigned to a particular functional area
(e.g. Section DC braking (DC-Break), PNU A51 to A55).
Setting the display parameters
In this section, you will see which parameters can be set using the
display on the keypad.
PNU Name Function
d01 Output frequency in Hz Output frequency display from 0.5 to 360 Hz. The Hz lamp on the keypad lights up.
d02
Motor current in A Display of the output current from 0.01 to 999.9 A. The A lamp on the keypad lights up.
d03
Direction of rotation Display:
F for clockwise rotation (forward),
r for anticlockwise rotation (reverse),
0 for stop
d04
Actual value x
factor Only with active PID closed loop control. The factor is set under PNU A75 and can have a value from
0.01 to 99.99; the default setting is 1.0.
d05
Status of digital inputs 1 to 5 Example: Digital inputs 1, 3 and 5 are activated. The digital inputs 2 and 4 are
deactivated.
d06
Digital outputs 11 and 12 and
fault message output
Example: The digital output 11 and the signal output K14 are activated. Digital
output 12 is deactivated.
d07
Output frequency x
factor The display of the product of the factor (PNU b86) and the output frequency in the range 0.01 to
99990.
Examples:
Display
11.11 corresponds to 11.11,
111.1 corresponds to 111.1,
1111. corresponds to 1111,
1111 corresponds to 11110.
d08
Last alarm indication Display of the most recent fault message and (after the PRG key is pressed) the output frequency,
motor current and DC bus voltage at the time the fault occurred. If a fault message is not available,
the display shows
---
d09 Older fault messages (fault
message register)
Display of the second from last and (after the PRG key is pressed) third from last fault message. If
neither the second last or third last fault message has been stored, the display shows
---
54321
K14 12 11