Fixed frequency FF1 to FF4
selection
61
External fault message EXT
If the digital input configured as EXT is activated, the fault
message E12 is initiated (e.g. an input used for the bimetal
contacts). The fault message remains active even if the EXT input
is deactivated again and must be acknowledged with a reset.
A reset can be carried out with:
• the RST input or
• the OFF key.
• Alternatively, the supply voltage can be switched off and on
again.
X Program one of the digital inputs 1 to 5 as EXT, by inputting the
value 12 under the respective PNU (C01 to C05).
Figure 55: Digital input 1 configured as FWD “start/stop clockwise
rotation” and digital input 3 as EXT “external fault”
Figure 56: Function chart for EXT (external fault message)
n
M
: motor speed
K14: signalling relay contact K14
a Motor coasts to a stop
Warning!
After a reset, the motor restarts immediately if a start
command (FWD or REV) is present.
EXT
FWD
P2413
FWD/REV
EXT
n
M
RST
K14
a