Setting Parameters
09/01 AWB8230-1412GB
102
Inhibit of the OFF key
The OFF key located on the keypad or remote operating unit can
be inhibited here.
Motor restart after cancellation of the FRS signal
Activation of the digital input configured as FRS causes the
inverter to shut down, leaving the motor to coast. Two methods
can be selected to deactivate the FRS input.
Display when a remote operating unit is used
The following operating data can be selected when the
DE5-KEY-RO3 remote operating unit is used:
PNU Name Adjustable in
RUN mode
Value Function WE
b87 OFF key
disabled
– 00 OFF key always active 00
01 OFF key not active with control via the FWD/REV terminals
PNU Name Adjustable in
RUN mode
Value Function WE
b88 Motor restart
after removal
of the FRS
signal
– 00 0 Hz restart after deactivation of the FRS input 00
01 Synchronization of the motor to the current motor speed after the delay
time entered under PNU b03.
PNU Name Adjustable in
RUN mode
Value Function WE
b89 Display when
the remote
operating unit
is used
j 01 Actual frequency 01
02 Motor current
03 Direction of rotation
04 PID actual value
05 Status of the digital inputs
06 Status of the digital outputs
07 Actual frequency multiplied by the frequency factor